Description
Hioki portable battery testers support the maintenance of UPS and storage batteries critical to the life support of all businesses. The 3554 sets the standard for assessing the deterioration and remaining life of lead-acid batteries by giving a complete diagnosis via battery resistance testing.The thresholds for determining the pass/fail condition of a battery depends on the specifications and standards of the battery manufacturer, battery type, capacity, etc. It is important and necessary to always conduct battery testing against the internal resistance and terminal voltage of a new or reference battery. In some cases, it may be difficult to determine the deterioration state of sealed lead acid batteries which demonstrates smaller changes in internal resistance than traditional open type (liquid) lead-acid or alkaline batteries.